Min/Max Setpoint adjustment

This command is used to set the possible min. and max. target temperature values.

Byte index

Hex value - Meaning

0

08 – The command code.

1

XX – lower temperature limit. Min. Default value: 0x00 (0°C).

2

XX – upper temperature limit. Max. Default value: 0x28 (40°C).

Example command: 0x081018 – Sets the lower temp. limit to 16°C and the upper temp. limit to 24°C.

The allowed lower temperature range is 0...38°C (1°C resolution).

The allowed upper temperature range is 0...40°C (1°C resolution).