Internal algorithm temporary state
This command allows to temporary disable the internal temperature control algorithm, thus stop adjusting the opening of the radiator valve.
The internal algorithm renews its operation when:
Target temp is changed manually (rotating the device outer ring),
By sending a downlink with new target temperature,
By re-enabling it via this very command, sending the appropriate parameter value.
Byte index
Hex value / Meaning
0
67 – command code
1
01 – Disable int. alg. operation temporarily; 00 – Enable int. alg. operation in case it was temporary disabled.
Example command: 0x6701 – temporary disable the int. alg.
Hex value – Meaning
Byte index
Sent request
Received response
0
68 – The command code.
68 – The command code.
1
As described in the corresponding set command.
Example command: 0x68
Example response: 0x6800 – internal temperature control algorithm is active.